Fire-resistant telescopic sliding doors are designed to separate fire compartments and are particularly suitable for locations where there is insufficient lateral space to accommodate conventional sliding doors. Thanks to their telescopic design, the individual gate sections slide behind one another when opened, making efficient use of the available space.
Depending on the specific design, the gates achieve fire resistance ratings from EW 15 to EW 90 and EI 15 to EI 90.
Fire-resistant telescopic sliding doors are particularly suitable for industrial and production halls, warehouses and logistics facilities, where fire compartments must be separated while making efficient use of the space around the building opening.
The door leaf consists of individual steel slats with fire-resistant infill, each independently suspended from a trolley.
The standard surface finish is galvanised steel sheet, with optional colours available according to the RAL colour chart.
The self-closing mechanism operates using a counterweight system, while a hydraulic speed regulator ensures a controlled and consistent closing speed.
Depending on the project requirements, the gate can be equipped with electric opening, integrated personnel doors or emergency exit doors, fire-resistant glazing, smoke-tight construction, stainless steel components, and additional activation and safety devices.
The gate leaf consists of multiple individual steel slats, each 300–1,100 mm wide. The slats are interconnected using a special joining system that leaves no visible protrusions or screw heads.
The total gate leaf thickness is 62 mm. Each slat has a surface made of 0.75 mm thick galvanised steel sheet, which is fully bonded to the fire-resistant infill.
The end-stop profile and labyrinth profiles are galvanised as standard.
The gate is equipped with a tubular handle on the side facing away from the wall and a recessed shell-shaped handle on the wall-facing side. The end position is secured by an end-stop buffer mounted on a bracket.
The gate is also equipped with a mechanism designed to facilitate easy manual operation during everyday use.
The gate can be installed on the following supporting structures, subject to the applicable structural and fire protection requirements: